The OH7525 series outdoor steel switchboards are designed for outdoor installation of 2G and 20G series industrial switches. Models are available with a backup power supply. A Wiring Diagram and Unit Test Report are included.
Outdoor steel switchboard with space for backup batteries. The switchboard meets the requirements of EN 61439-1 (certified by TUV SUD) and is optimized especially for outdoor installations of industrial switches, PLCs and METEL IO modules. The switchboard can also be equipped with devices from other manufacturers. The switchboard is equipped with the following components 230VAC socket type E (CZ), backup power supply 48VDC/240W, surge protector 1st + 2nd stage, circuit breaker 10A, current protector, dimensions: 700x500x250 mm
Order code: 7-211-210
Availability: Full-scale production
Outdoor steel switchboard with space for backup batteries. The switchboard meets the requirements of EN 61439-1 (certified by TUV SUD) and is optimized especially for outdoor installations of industrial switches, PLCs and METEL IO modules. The switchboard can also be equipped with devices from other manufacturers. The switchboard is equipped with the following components 230VAC socket type F (DE), backup power supply 48VDC/240W, surge protector 1st + 2nd stage, circuit breaker 10A, current protector, dimensions: 700x500x250 mm
Order code: 7-211-220
Availability: Full-scale production
| MECHANICS | |
|---|---|
| Dimensions - h / w / d | 700 x 500 x 250 mm |
| Pins | 10 (PG11) |
| Material and finish | Galvanised steel with epoxy polyester (grey RAL 7035) |
| Weight | Max. 20 kg (without batteries) |
| Tamper | Contact NC |
| Maximum size of 1pc battery - h/w/w | 180 x 197 x 180 mm |
| Mechanical protection | IK10 |
| Degree of coverage | IP66 / IP55 (with thermoset) |
| JISTIČ | |
|---|---|
| Rated working voltage | 230 VAC |
| Rated current | 10 A |
| Tripping characteristic | C |
| Rated short-circuit capability | 6 kA |
| SURGE PROTECTION | |
|---|---|
| Type | T1, T2, T3 |
| Rated AC operating voltage | 230 VAC |
| Voltage protection level at the In input | 1,25 kV |
| Pulse discharge current for Class I test (10/350) | 12.5 kA |
| CURRENT PROTECTOR | |
|---|---|
| Rated working voltage | 30 mA |
| Type | A |
| Rated residual current | 30 mA |
| Rated short-circuit capability | 6 kA |
| BACKUP POWER SUPPLY (AND ACCESSORIES) | |
|---|---|
| Input voltage (50 Hz) | 115 - 230 - 277 VAC (90 - 135 VAC / 180 - 305 VAC) |
| Rated power | 240 W |
| Output voltage (Vn) / rated current (In) | 48 VDC / 5A (switch-on delay max. 1.5 s) |
| Short circuit / overload / overheating protection | Yes (support for running with capacity load) |
| Battery output | 4pcs of series connected 12 V batteries |
| Supported batteries | Lead acids, AGM, GEL |
| Relay 1 (C-NC-NO) | Relay max. 30 VDC / 1 A | Main or backup input power supply |
| Relay 2 (C-NC-NO) | Relay max. 30 VDC / 1 A | Malfunctioning system / weak battery |
| Battery Output Protection | Two-pole fuse holder with 6A gG fuses |
| Output protection 48 VDC | Circuit breaker |
| Shelf for batteries | 4x 36 Ah |
| SOCKET 230 VAC | |
|---|---|
| Rated working voltage | 230 VAC |
| Type E | With protective pin |
| Type F | Schuko design |
| OH-THERMO-SET-HV - VENTILATION AND HEATING SYSTEM (optional accessory) | |
|---|---|
| Fan | Controlled by thermostat | 1 | 0 - 60 °C |
| Heating | Controlled by thermostat | 250 W | 0 - 60 °C |
| SD - VIBRATION DETECTOR (optional accessory) | |
|---|---|
| Alarm output | Relay |
| BATTERIES TESTED | |
|---|---|
| LONG U1-36HE | 12 V, 36 Ah |
| EMC and safety | ||
|---|---|---|
| EN 61439-1 | Low voltage switchboards | |
Temperature sensor to adjust the battery charging voltage depending on the battery temperature.
No. Batteries are not part of the switchboard and no batteries can be ordered in our range.
No. Our back-up switchboards include a 48 VDC back-up power supply that is used to power PoE powered switches.