IO boards

  • Installation on the PLC motherboard or as a stand-alone IO module
  • A wide range of digital and analog inputs and outputs
  • Highly durable hardware with integrated surge protectors
  • Operating temperature from −40°C to +70°C

The individual PCBs cannot be ordered; they are provided solely for the purpose of listing all available interfaces, communication protocols, inputs and outputs.

IO boards are universally applicable for connection to a PLC motherboard or as a standalone IO module. Most boards feature an IF slot for fitting an IF module, which communicates using the Modbus RTU protocol.

Models

Inputs:

? ? ? ? ? ? ?

Outputs:

? ? ? ? ? ? ? ?

AI8.1-PCB

8x 12-bit analog U/I input, 2x NOC 24V relay output, 2x NO 230V relay output, 1x IF slot, operating temperature -40°C to +70°C, 600W integrated surge protection. Designed for BOX and DIN series.

Order code: 0000-0200

Availability: Unavailable

AI4.1-PCB

4x 24-bit analog RTD inputs, 4x SSR outputs, 4x 24 V digital inputs, 1x IF slot, operating temperature -40°C to +70°C, 600 W integrated surge protection. Designed for BOX and DIN series.

Order code: 0000-0300

Availability: Unavailable

DI8.1-PCB

8x 24V digital inputs, 4x NO 230V relay outputs, 2x PUSH-PULL transistor outputs, 1x IF slot, operating temperature -40°C to +70°C, 600W integrated surge protection. Designed for BOX and DIN series.

Order code: 0000-0100

Availability: Unavailable

AO8.1-PCB

8x 12-bit analog output, 4x 12-bit analog U input, 4x digital 24V input, 1x IF slot, operating temperature -40°C to +70°C, 600W integrated surge protection. Designed for BOX and DIN series.

Order code: 0000-0600

Availability: Unavailable

RE8.1-PCB

8x NO 230V relay outputs, 3x optically isolated 230V inputs, 2x NOC 230V relay outputs, 1x IF slot, operating temperature -40°C to +70°C, 600W integrated surge protection. Designed for BOX and DIN series.

Order code: 0000-0500

Availability: Unavailable

BI8.1-PCB

8x 10-bit alarm/digital 5V inputs, 3x digital 5V inputs, 1x NOC 24V relay output, 2x open-collector NPN outputs, 1x IF slot, operating temperature -40°C to +70°C, 600 W integrated surge protector. Designed for BOX and DIN series.

Order code: 0000-0400

Availability: Unavailable

BO8.1-PCB

8x 8-bit alarm output, 3x 10-bit alarm/digital 5V input, 2x open-collector NPN outputs, 1x NOC 24V relay output, 1x IF slot, operating temperature -40°C to +70°C, 600 W integrated surge protector. Designed for BOX and DIN series.

Order code: 0000-0800

Availability: Unavailable

RE8.3E-PCB

8x NOC 24V relay outputs, 1x RS485, operating temperature -40°C to +70°C, 600 W integrated surge protection. Designed for DIN series.

Order code: 0000-1100

Availability: Unavailable

RE8.2E-PCB

8x NOC 24V relay outputs, operating temperature -40°C to +70°C, 600 W integrated surge protector. Designed for BOX series, cannot be used as a standalone IO module.

Order code: 0000-0900

Availability: Unavailable

RE8.2-PCB

8x NOC 24V relay output, 1x IF slot, operating temperature -40°C to +70°C, 600 W integrated surge protection. Designed for BOX series.

Order code: 0000-1000

Availability: Unavailable

BI8.2E-PCB

8x 10-bit alarm / digital 5V inputs, 1x RS485, operating temperature -40°C to +70°C, integrated surge protector 600 W. Designed for DIN series.

Order code: 0000-1200

Availability: Unavailable

PP8.1-PCB

8x PUSH-PULL transistor outputs, 4x 24V digital inputs, 3x 10bit alarm/digital 5V inputs, 1x NOC 24V relay output, 1x IF slot, operating temperature -40°C to +70°C, 600W integrated surge protector. Designed for BOX and DIN series.

Order code: 0000-0700

Availability: Unavailable

BI8.4-PCB

8x 10-bit alarm / digital 5V inputs, 4x NOC 24V relay outputs, 1x IF slot, operating temperature -40°C to +70°C, 600 W integrated surge protection. Designed for BOX series.

Order code: 0000-1300

Availability: Unavailable

BI8.4E-PCB

8x 10-bit alarm / digital 5V inputs, 4x NOC 24V relay outputs, 1x RS485, operating temperature -40°C to +70°C, 600 W integrated surge protection. Designed for DIN series.

Order code: 0000-1400

Availability: Unavailable

Specifications

Technical parameters
POWER
Input voltage range10 - 60 VDC
ENVIRONMENT AND SURGE PROTECTIONS
I/O surge protectionsMin. 600 W (10/1000 µs)
Operating temperature–40…+70 °C
Storage temperature–40…+70 °C / Max. 95 % humidity
12-BIT ANALOG CURRENT OR VOLTAGE INPUTS (with galvanic isolation)
Voltage ranges±2.5V, ±5V, ±10V, 0V to 5V, 0V to 10V
Current ranges0 to 20mA, 4 to 20mA
Sampling rate1 kSps (adaptive)
24-BIT RTD INPUTS
Resistive rangesPT100, PT1000 (3-wires connection)
Sampling rate1 kSps
Isolation voltage1.000 VRMS (RTDx / CPU)
SSR OUTPUTS
Output typeMOSFET (SPST contact type)
Voltage / current75 VAC to 264 VAC, 45 to 65 Hz / Max. 1 A, minimal 20 mA
Breakdown voltage3.000 Vrms (Input / Output)
Isolation voltage between SSR outputs1.500 Vrms
24 V DIGITAL INPUTS (with galvanic isolation 2.500 Vrms between inputs and CPU)
Input voltage DC / AC | Input currentLog. 0: −30 V to 5 V, Log. 1: +15 V to 30 V | 12 mA at 24 VDC
Maximum input voltage50 V / 1 s
NOC 24 V RELAY OUTPUTS (changeover contact)
Max. load0.5 A / 120 VAC, 1 A / 24 VDC (resistive load)
Electrical lifetime3,000,000 operations
Isolation voltage1.000 Vrms / 1 min. (terminals to electronic or case)
NO 230 V RELAY OUTPUTS (normal open contact)
Max. load5 A / 250 VAC, 3 A / 30 VDC (resistive load)
Electrical lifetime100,000 operations at 250 VAC / 5A
Isolation voltage2.500 Vrms / 1 min. (terminals to electronic or case)
NOC 230 V RELAY OUTPUTS (changeover contact)
Max. load10 A / 250 VAC, peak 15 A, (resistive load)
Electrical lifetime50.000 operations, minimal value
Isolation voltage2.500 Vrms / 1 min. (terminals to electronic or case)
ALARM / 5 V DIGITAL INPUTS
Alarm / digital mode usagePIR / tampers (input voltage max. 7VDC)
Dry contact schematicLog. 0: open, Log. 1: close to ground
Alarm mode rangeFrom 10 to 30.000 Ω (10-bit resolution)
5 V DIGITAL INPUTS
Input voltageMax. 7 VDC
Dry contact schematicLog. 0: open, Log. 1: close to ground
OPEN COLLECTOR NPN TRANSISTORS OUTPUTS
Internal Pull-Up1,000 Ω, ON/OFF by a DIP switch
Maximum load (sinking | sourcing)16 V / 250 mA | 12 V / 1 mA
8-BIT ALARM OUTPUTS
Adjustable range200 to 50 000 Ω
PUSH-PULL TRANSISTOR OUTPUTS
Output typeOpen collector NPN or PNP, Push-Pull (software selectable)
Maximum load30 V / 0.25 A
Galvanic isolation2.500 VRMS (PP x output / CPU)
Shortcut protectionYes (polyswitch)
230 V DIGITAL INPUTS
Input voltage ACLog. 0: 0 VAC to 120 VAC, Log. 1: 200 VAC to 250 VAC
Isolation voltage2.500 Vrms, (IN x / CPU)
Standards and protocols, EMC and safety
EMC and safety
EN 61000-6-2Immunity - industrial environment
IEEE 1613Environmental and Testing Requirements | Electric Power Substations
EN 50130-4 ed. 2Alarm systems - Part 4: Electromagnetic compatibility
EN 55035EMC of multimedia devices - immunity requirements
EN 55032EMC of multimedia devices - emission requirements
EN 61131-2Programmable control units
EN 62368-1Safety requirements of Information technology equipment
EN IEC 63000The Assessment Of Electrical And Electronic Products With Respect To The ROHS
Standards and protocols
EN 61131-2Programmable controllers