The individual PCBs cannot be ordered; they are provided solely for the purpose of listing all available interfaces, communication protocols, inputs and outputs.
IO boards are universally applicable for connection to a PLC motherboard or as a standalone IO module. Most boards feature an IF slot for fitting an IF module, which communicates using the Modbus RTU protocol.
8x 12-bit analog U/I input, 2x NOC 24V relay output, 2x NO 230V relay output, 1x IF slot, operating temperature -40°C to +70°C, 600W integrated surge protection. Designed for BOX and DIN series.
Order code: 0000-0200
Availability: Unavailable
4x 24-bit analog RTD inputs, 4x SSR outputs, 4x 24 V digital inputs, 1x IF slot, operating temperature -40°C to +70°C, 600 W integrated surge protection. Designed for BOX and DIN series.
Order code: 0000-0300
Availability: Unavailable
8x 24V digital inputs, 4x NO 230V relay outputs, 2x PUSH-PULL transistor outputs, 1x IF slot, operating temperature -40°C to +70°C, 600W integrated surge protection. Designed for BOX and DIN series.
Order code: 0000-0100
Availability: Unavailable
8x 12-bit analog output, 4x 12-bit analog U input, 4x digital 24V input, 1x IF slot, operating temperature -40°C to +70°C, 600W integrated surge protection. Designed for BOX and DIN series.
Order code: 0000-0600
Availability: Unavailable
8x NO 230V relay outputs, 3x optically isolated 230V inputs, 2x NOC 230V relay outputs, 1x IF slot, operating temperature -40°C to +70°C, 600W integrated surge protection. Designed for BOX and DIN series.
Order code: 0000-0500
Availability: Unavailable
8x 10-bit alarm/digital 5V inputs, 3x digital 5V inputs, 1x NOC 24V relay output, 2x open-collector NPN outputs, 1x IF slot, operating temperature -40°C to +70°C, 600 W integrated surge protector. Designed for BOX and DIN series.
Order code: 0000-0400
Availability: Unavailable
8x 8-bit alarm output, 3x 10-bit alarm/digital 5V input, 2x open-collector NPN outputs, 1x NOC 24V relay output, 1x IF slot, operating temperature -40°C to +70°C, 600 W integrated surge protector. Designed for BOX and DIN series.
Order code: 0000-0800
Availability: Unavailable
8x NOC 24V relay outputs, 1x RS485, operating temperature -40°C to +70°C, 600 W integrated surge protection. Designed for DIN series.
Order code: 0000-1100
Availability: Unavailable
8x NOC 24V relay outputs, operating temperature -40°C to +70°C, 600 W integrated surge protector. Designed for BOX series, cannot be used as a standalone IO module.
Order code: 0000-0900
Availability: Unavailable
8x NOC 24V relay output, 1x IF slot, operating temperature -40°C to +70°C, 600 W integrated surge protection. Designed for BOX series.
Order code: 0000-1000
Availability: Unavailable
8x 10-bit alarm / digital 5V inputs, 1x RS485, operating temperature -40°C to +70°C, integrated surge protector 600 W. Designed for DIN series.
Order code: 0000-1200
Availability: Unavailable
8x PUSH-PULL transistor outputs, 4x 24V digital inputs, 3x 10bit alarm/digital 5V inputs, 1x NOC 24V relay output, 1x IF slot, operating temperature -40°C to +70°C, 600W integrated surge protector. Designed for BOX and DIN series.
Order code: 0000-0700
Availability: Unavailable
8x 10-bit alarm / digital 5V inputs, 4x NOC 24V relay outputs, 1x IF slot, operating temperature -40°C to +70°C, 600 W integrated surge protection. Designed for BOX series.
Order code: 0000-1300
Availability: Unavailable
8x 10-bit alarm / digital 5V inputs, 4x NOC 24V relay outputs, 1x RS485, operating temperature -40°C to +70°C, 600 W integrated surge protection. Designed for DIN series.
Order code: 0000-1400
Availability: Unavailable
| POWER | |
|---|---|
| Input voltage range | 10 - 60 VDC |
| ENVIRONMENT AND SURGE PROTECTIONS | |
|---|---|
| I/O surge protections | Min. 600 W (10/1000 µs) |
| Operating temperature | –40…+70 °C |
| Storage temperature | –40…+70 °C / Max. 95 % humidity |
| 12-BIT ANALOG CURRENT OR VOLTAGE INPUTS (with galvanic isolation) | |
|---|---|
| Voltage ranges | ±2.5V, ±5V, ±10V, 0V to 5V, 0V to 10V |
| Current ranges | 0 to 20mA, 4 to 20mA |
| Sampling rate | 1 kSps (adaptive) |
| 24-BIT RTD INPUTS | |
|---|---|
| Resistive ranges | PT100, PT1000 (3-wires connection) |
| Sampling rate | 1 kSps |
| Isolation voltage | 1.000 VRMS (RTDx / CPU) |
| SSR OUTPUTS | |
|---|---|
| Output type | MOSFET (SPST contact type) |
| Voltage / current | 75 VAC to 264 VAC, 45 to 65 Hz / Max. 1 A, minimal 20 mA |
| Breakdown voltage | 3.000 Vrms (Input / Output) |
| Isolation voltage between SSR outputs | 1.500 Vrms |
| 24 V DIGITAL INPUTS (with galvanic isolation 2.500 Vrms between inputs and CPU) | |
|---|---|
| Input voltage DC / AC | Input current | Log. 0: −30 V to 5 V, Log. 1: +15 V to 30 V | 12 mA at 24 VDC |
| Maximum input voltage | 50 V / 1 s |
| NOC 24 V RELAY OUTPUTS (changeover contact) | |
|---|---|
| Max. load | 0.5 A / 120 VAC, 1 A / 24 VDC (resistive load) |
| Electrical lifetime | 3,000,000 operations |
| Isolation voltage | 1.000 Vrms / 1 min. (terminals to electronic or case) |
| NO 230 V RELAY OUTPUTS (normal open contact) | |
|---|---|
| Max. load | 5 A / 250 VAC, 3 A / 30 VDC (resistive load) |
| Electrical lifetime | 100,000 operations at 250 VAC / 5A |
| Isolation voltage | 2.500 Vrms / 1 min. (terminals to electronic or case) |
| NOC 230 V RELAY OUTPUTS (changeover contact) | |
|---|---|
| Max. load | 10 A / 250 VAC, peak 15 A, (resistive load) |
| Electrical lifetime | 50.000 operations, minimal value |
| Isolation voltage | 2.500 Vrms / 1 min. (terminals to electronic or case) |
| ALARM / 5 V DIGITAL INPUTS | |
|---|---|
| Alarm / digital mode usage | PIR / tampers (input voltage max. 7VDC) |
| Dry contact schematic | Log. 0: open, Log. 1: close to ground |
| Alarm mode range | From 10 to 30.000 Ω (10-bit resolution) |
| 5 V DIGITAL INPUTS | |
|---|---|
| Input voltage | Max. 7 VDC |
| Dry contact schematic | Log. 0: open, Log. 1: close to ground |
| OPEN COLLECTOR NPN TRANSISTORS OUTPUTS | |
|---|---|
| Internal Pull-Up | 1,000 Ω, ON/OFF by a DIP switch |
| Maximum load (sinking | sourcing) | 16 V / 250 mA | 12 V / 1 mA |
| 8-BIT ALARM OUTPUTS | |
|---|---|
| Adjustable range | 200 to 50 000 Ω |
| PUSH-PULL TRANSISTOR OUTPUTS | |
|---|---|
| Output type | Open collector NPN or PNP, Push-Pull (software selectable) |
| Maximum load | 30 V / 0.25 A |
| Galvanic isolation | 2.500 VRMS (PP x output / CPU) |
| Shortcut protection | Yes (polyswitch) |
| 230 V DIGITAL INPUTS | |
|---|---|
| Input voltage AC | Log. 0: 0 VAC to 120 VAC, Log. 1: 200 VAC to 250 VAC |
| Isolation voltage | 2.500 Vrms, (IN x / CPU) |
| EMC and safety | ||
|---|---|---|
| EN 61000-6-2 | Immunity - industrial environment | |
| IEEE 1613 | Environmental and Testing Requirements | Electric Power Substations | |
| EN 50130-4 ed. 2 | Alarm systems - Part 4: Electromagnetic compatibility | |
| EN 55035 | EMC of multimedia devices - immunity requirements | |
| EN 55032 | EMC of multimedia devices - emission requirements | |
| EN 61131-2 | Programmable control units | |
| EN 62368-1 | Safety requirements of Information technology equipment | |
| EN IEC 63000 | The Assessment Of Electrical And Electronic Products With Respect To The ROHS | |
| Standards and protocols | |
|---|---|
| EN 61131-2 | Programmable controllers |