FO-485 are digital optical transmitters of the ZETTLER EXPERT fire protection system bus.
The exclusive distributor of this product is Tyco Fire & Integrated Solutions s.r.o.
Digital RS485 optocouplers for EPS system ZETTLER EXPERT - Tx1310nm, Rx1550nm
Order code: 1-506-784
Availability: Production to order
Digital RS485 optocouplers for EPS system ZETTLER EXPERT - set
Order code: 1-006-780
Availability: Production to order
Digital RS485 optocouplers for EPS system ZETTLER EXPERT - Tx1550nm, Rx1310nm
Order code: 1-506-785
Availability: Production to order
| OPTICAL | |
|---|---|
| Optical power | -14 - -8 / -10 - 0 dBm (SM / MM) |
| Sensitivity | -31 dBm (SM / MM) |
| Optical fibre | 1x SM 8(9)/125 - SC connectors µm (PC sanding) |
| Optical fibre | 1x MM 50(62,5)/125 - SC connectors µm (PC sanding) |
| RANGE TDW ... RDW | |
|---|---|
| Multimode 50/125 μm | Max. 6 km |
| Multimode 62.5/125 μm | Max. 4 km |
| Singlemode 9/125 μm | Max. 20 km |
| WAVE LENGHTS | |
|---|---|
| ...W4 Tx/Rx | 1310/1550 nm |
| ...W5 Tx/Rx | 1550/1310 nm |
| POWER | |
|---|---|
| Voltage | 4,5 - 5,5 VDC |
| Current at 5VDC | Max. 250 mA |
| ENVIRONMENT | |
|---|---|
| Operating temperature | -40 - +70 °C (ambient temperature) |
| Humidity | Max. 95 % (noncondensing) |
| MECHANICAL | |
|---|---|
| Dimensions - h / w / d | 50 x 15 x 56 mm |
| Weight | type: 40 g (including accessories) |
| EMC and safety | ||
|---|---|---|
| EN 61000-6-2 | Immunity - industrial environment | |
| IEEE 1613 | Environmental and Testing Requirements | Electric Power Substations | |
| EN 50130-4 ed. 2 | Alarm systems - Part 4: Electromagnetic compatibility | |
| EN 55035 | EMC of multimedia devices - immunity requirements | |
| EN 55032 | EMC of multimedia devices - emission requirements | |
| EN 62368-1 | Safety requirements of Information technology equipment | |
| EN IEC 63000 | The Assessment Of Electrical And Electronic Products With Respect To The ROHS | |
| Standards and protocols | |
|---|---|
| Serial line | RS485 |